Intertek REPORT NUMBER: 100978606 MID-001 ORIGINAL ISSUE DATE: DECEMBER 18, 2012 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 RENDERED TO INSULATING COATINGS CORP. 27 LINK DRIVE SUITED BINGHAMTOM, NY 13905 CONTACT: MR. DEAN BODDIFORD dboddiford@icc-astec.com PRODUCT EVALUATED: Astec Re-Ply Roofing System, EVALUATION PROPERTY: ASTM E108, “Standard Methods for Fire Tests of Roof Coverings” TEST REPORT Report of Testing Insulating Coatings Corp’s Re-Ply Roofing for compliance with the applicable requirements of ASTM E108 (2010) “Standard Test Methods for Fire Tests of Roof Coverings” and UL 790 (2004). This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek’s responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek, The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Intertek Intertek Intertek Intertek Intertek Intertek Intertek
Background image
Intertek Insulating Coatings Corp Date: December 18, 2012 Project No. 100978606MID-001 Page 2 of 10 1 Table of Contents T TbIE B COMBITEL = . e by i s « sufeinsdon s 18 P st o 2 & ATIOCIUCTIORY., . e o 1 nhifiionss b 2 isbeihe § f o onbbsd s s s bt 0 ) 3. TESLSAMPIEE. o im s oty v s ue Sy i 1 emmeied T e B % 8 4 Testing and Evaluation Methods....................ccooioiii 4 B T OBl RIS iy oo o mmmmsmin s o 5 it a0 e i B 0 8 4 Ol AR BO M incmnis £y 3 hmsistussis s 85 Doinnfimbmminti o o S s i e 4 2.2, ‘Results:and Observations. ... ... i it ssiee s et and e 63 5
Background image
Intertek Insulating Coatings Corp Date: December 18, 2012 Project No. 100978606MID-001 Page 3 of 10 2 Introduction Intertek Testing Services NA (Intertek) Fire Testing Laboratory in Middleton, Wisconsin conducted an investigation of the external fire resistance characteristics of Insulating Coatings Corp’s B.U.R. roofing system, for class “A” application. This system is intended for installation over a non-combustible roof, therefore only the Spread of Flames tests were conducted. The samples were received at the laboratory December 3, 2012 in good condition. The tests were conducted in accordance with ASTM E108 (2010) “Standard Test Methods for Fire Tests of Roof Coverings” and UL 790 (2004). 3 Test Samples The plywood decks were constructed by Intertek technicians according to the specifications of test standard ASTM E108 (2010) “Standard Test Methods for Fire Tests of Roof Coverings”. 1. The test material was submitted by the client. 2. The test material was applied by Intertek technicians. The samples are described in more detail in the table below. Deck# Deck Type Deck System Material 1 Spread of Flames 15/32" 2" GP Dens Deck. A-C Plywood | Astec 2000 Base Coat at 1 gallons per 100 square feet. (24 Hr. cure.) Astec 2000 Base Coat at 3/4 gallons per 100 square feet over a polyester cloth. (No cure time). Astec 2000 Base Coat at 3/4 gallons per 100 square feet. (24 Hr. cure) Astec 2000 Finish Coat at 3/4 gallons per 100 square feet. (3 Hr. cure) Astec 2000 Finish Coat at 3/4 gallons per 100 square feet. (48 Hr. cure) 2 Spread of Flames 15/32" 2" GP Dens Deck. A-C Plywood | Astec 2000 Base Coat at 1 gallons per 100 square feet. (24 Hr. cure.) Astec 2000 Base Coat at 3/4 gallons per 100 square feet over a polyester cloth. (No cure time). Astec 2000 Base Coat at 3/4 gallons per 100 square feet. (24 Hr. cure) Astec 2000 Finish Coat at 3/4 gallons per 100 square feet. (3 Hr. cure) Astec 2000 Finish Coat at 3/4 gallons per 100 square feet. (48 Hr. cure) NOTE: The ASTEC 2000 MULTI-LAYER COATING SYSTEM will result in a minimum 4.0 gallons per 100 sqft system resulting in no less than 35-40 mils DFT.
Background image
Intertek Insulating Coatings Corp Date: December 18, 2012 Project No. 100978606MID-001 Page 4 of 10 4 Testing and Evaluation Methods The tests were conducted in accordance with ASTM E108 (2010) “Standard Test Methods for Fire Tests of Roof Coverings” and UL 790 (2004). . 5 Test Results 5.1. Calibration Test Conditions (Class A) Test Date 12/13/2012 Air Velocity 1056 +/-44 fpm Slope of Cal. Deck 5:12 Average flame temp 1404°F Ambient air temp. 1.0 Test Conditions (Class A) Test Date 12/17/2012 Air Velocity 1056 +/-44 fpm Slope of Cal. Deck 5:12 Average flame temp 1396°F Ambient air temp. 72°F
Background image
Intertek Insulating Coatings Corp Project No. 100978606MID-001 5.2. Results and Observations Spread of Flames Tests Test Observations Deck: 1 Date: December 18, 2012 Page 5 of 10 Test Date 12/13/2012 Slope of Test Deck 5:12 Ambient Temperature 66°F Time Distance (min:sec) | (feet-inches) | Observations/Comments 00:00 Burner ignited. 00:18 Surface begins to blister. 02:03 Surface ignition. 03:14 Flame goes out. 05:00 Surface ignition. 05:24 1 07:49 Flame out. 10:00 Test stop. Acceptance Level: Class ‘A’, maximum spread of flames is 1’ 8”. Test Observations Deck: 2 Test Date 12/17/2012 Slope of Test Deck 512 Ambient Temperature 81°F Time Distance (min:sec) | (feet-inches) Observations/Comments 00:00 Burner ignited. 01:00 Surface begins to blister. 05:50 Attached flame on surface. 05:55 1 10:00 Test stop. Acceptance Level: Class ‘A’, maximum spread of flames is 1’ 4”.
Background image
Intertek Insulating Coatings Corp Project No. 100978606MID-001 6 Conclusion The tests were conducted in accordance with ASTM E108 (2010) “Standard Test Methods for Fire Tests of Roof Coverings” and UL 790 (2004). Below is a summary of the test results. Sample # Test Slope Rating 1 Spread of Flames 512 Class ‘A’ 2 Spread of Flames 512 Class ‘A’ The Astec Re-Ply roofing system installed as stated in this report, applied over a non- combustible deck, met the requirement for a class A fire application in accordance with ASTM E108 (2010) “Standard Test Methods for Fire Tests of Roof Coverings” and UL 790 (2004)at a 5:12 slope. This report does not automatically imply product certification. compliance. INTERTEK TESTING SERVICES NA Reported by: Reviewed by: %%W Gregory Allen Associate Engineer, Fire Building Products Intertek Rick Curkeet, P E. Chief Engineer, Building Products Intertek Date: December 18, 2012 Page 6 of 10 Products must be under a certification program and bear the Warnock Hersey registered certification mark to demonstrate
Background image
Intertek Insulating Coatings Corp Date: December 18, 2012 Project No. 100978606MID-001 Page 7 of 10 APPENDIX A Photos
Background image
Intertek Insulating Coatings Corp Project No. 100978606MID-001 Photographs Test 1 il -WA:..\U\: ’hl’“'“ pROJE | (06 1 EGI? Date: December 18, 2012 Page 8 of 10
Background image
Intertek Insulating Coatings Corp Date: December 18, 2012 Project No. 100978606MID-001 Page 9 of 10 sty -’fl"l‘{- o pATES NiE .\lv\(\'ll.\ll";f I3 TESHCUASSE 7} T
Background image
Intertek Insulating Coatings Corp Date: December 18, 2012 Project No. 100978606MID-001 Page 10 of 10 REVISION SUMMARY DATE SUMMARY 12/18/2012 Initial report
Background image